	PRODUCT PARAMETERS:
Executive standards: IEC, GB, ANSI/IEEE, NEMA
Capacity: 50kVA~40000 kVA
Primary side rated voltage: 33kV~38.5kVA
Rated voltage on secondary side: 0.4kV~11kVA
Number of tap off gears: 5-9
Frequency: 50/60 Hz
Number of phases: three-phase
Connection group: Dyn11/YynO/Yd11/YNd11, etc
Impedance: 6.5%~10
 
| 
 Rated capacity KVA | Level 1 | Level 2 | Level 3 | 
					short circuit 
 % | |||
| Empty loss 
 W | Load loss 
 W | Empty loss 
 W | Load loss 
 W | Empty loss 
 W | Load loss 
 W | ||
| 3150 | 1.7 | 20.7 | 2.0 | 20.7 | 2.4 | 21.9 | 7 | 
| 4000 | 2.0 | 24.6 | 2.3 | 24.6 | 2.9 | 25.9 | |
| 5000 | 2.4 | 28.2 | 2.8 | 28.2 | 3.5 | 29.7 | |
| 6300 | 2.9 | 31.5 | 3.4 | 31.5 | 4.2 | 33.3 | 8 
 | 
| 8000 | 4.0 | 34.6 | 4.7 | 34.6 | 5.8 | 36.5 | |
| 10000 | 4.8 | 40.8 | 5.7 | 40.8 | 7.0 | 43.0 | |
| 12500 | 5.5 | 48.4 | 6.5 | 48.4 | 8.0 | 51.1 | |
| 16000 | 6.7 | 59.2 | 7.9 | 59.2 | 9.7 | 62.5 | |
| 20000 | 7.9 | 71.6 | 9.4 | 71.6 | 11.5 | 75.5 | |
| 25000 | 9.4 | 84.6 | 11.1 | 84.6 | 13.6 | 89.3 | 10 
 | 
| 31500 | 11.1 | 100.8 | 13.1 | 100.8 | 16.2 | 106.4 | |